Normally in stability simulations, it is imperative to run a no fault simulation or what they call flat run to verify that dynamic models are behaving in a manner without disturbance thus expecting flat plots of parameters.
Generator angles for no fault simulation. |
A stub fault is another practical test if the response of the dynamic models is correct for a simple and fast fault disturbance. Here are example plots from a stub fault at bus 1 at 1.0 seconds and cleared after 0.1 seconds without tripping any line.
Generator angles for stub fault simulation. |
Generator speed for stub fault simulation. |
Bus frequency for stub fault simulation. |
Bus voltages for stub fault simulation. |
References:
[1] Power Systems Test Case Archive. Available on-line: http://www.ee.washington.edu/research/pstca/dyn30/pg_tcadyn30.htm
[2] Pablo Ledesma, New England Test System, IEEE 39 Bus System, 10 generators, in PSS/E format (version 29). Departamento de IngenierĂa ElĂ©ctrica Universidad Carlos III de Madrid. Available on-line: http://electrica.uc3m.es/pablole/new_england.html