I followed the references [1-3] for assuming models for each generation considering fuel types. Also, combined with these good sources, PowerWorld provides default data for the dynamic models including the generic wind generation dynamic models (for NorthWind generation, north of Luzon) and loads (motors and discharge lighting, etc).
For generation using diesel as fuel, I initially modeled the machine as GENSAL but WECC has indicated to use GENTPJ instead for reasons cited in reference [4].
As I'm using PowerWorld, I made advantage of the auto correction of dynamic data and proceeded with the validation of models.
As mentioned in other posts, I simulated flat runs and had the models respond as expected. The following plots are simulated three-phase faults where fault clearing time is in accordance with the Philippine Grid Code and assuming a single-line contingency.
Bus Voltages Plots for Fault on Balintawak 230 kV, tripping Balintawak-Araneta 230 kV Line (Luzon) |
Rotor Angles Plots for Fault on Balintawak 230 kV bus, tripping Balintawak-Araneta 230 kV Line (Luzon) |
Bus Frequency Plots for Fault on Lugait 138 kV bus, tripping Lugait - Tagaloan 138 kV Line (Mindanao) |
Generator Speed Plots for Fault on Lugait 138 kV bus, tripping Lugait - Tagaloan 138 kV Line (Mindanao) |
Various Plots for Fault at Quiot 138 kV bus, tripping Quiot-Banilad 138 kV Line (Visayas) |
I'm planning to write a full paper on this work and if you are interested in the models or collaborate with me, drop me a message at ebcano@gmail.com.
References:
[1] IEEE Recommended Practice for Excitation System Models for Power System Stability Studies, IEEE Std 421.5-1992
[2] IEEE PES Working Group, Hydraulic Turbine and Turbine Control Models for System Dynamic, IEEE Transaction on Power System 7 (1992) 167-174.
[3] Dynamic Models Package Standard 1. Available: http://www.energy.siemens.com/hq/pool/hq/services/power-transmission-distribution/power-technologies-international/software-solutions/Dynamic_Models_Package_Standard-1.pdf
[4] Additional Information on GENTPJ Model. Available: http://www.wecc.biz/library/WECC%20Documents/Documents%20for%20Generators/Generator%20Testing%20Program/gentpj%20and%20gensal%20morel.pdf